- Brand Name: HKNA
- Origin: CN(Origin)
- Certification: CE
- Place of Origin: Hebei, China
- Brand Name: FORERUN
- Model Number: FRDM-96-EF/C
- Display Type: Digital Only
- Phase: Three Phase
- Measuring Energy Range: 10000,40000,160000 imp/kWh
- Accuracy Class: Grade 0.5
- Output Voltage: AC 250V/3A,DC 30V/3A
- Operating Temperature: -10℃~ 55℃
- Dimensions: 96mm
- Product Name: Multi function power meter
|
technical parameter
|
index
|
||||||
|
input |
network
|
Three phase three wire, three phase four wire
|
|||||
|
frequency
|
45~65Hz
|
||||||
|
Voltage
|
Rated value:AC 100V、400V
|
||||||
|
Overload: 1.2 times of rated value (continuous);
2 times of rated value for 1 second
|
|||||||
|
power waste: ≤ 0.2VA
|
|||||||
|
Electric current
|
Rating:AC 1A、5A
|
||||||
|
Overload: 1.2 times of rated value (continuous);
10 times of rated value for 1 second
|
|||||||
|
power waste: ≤ 0.2VA
|
|||||||
|
output |
electric energy
|
Output mode: optocoupler pulse with open collector,
2-way output (optional)
|
|||||
|
Pulse constant: 10000、40000、160000 imp/kWh etc.
|
|||||||
|
communication
|
RS485 Interface、Modbus-RTU、 agreement
|
||||||
|
display
|
LED、LCD
|
||||||
|
function |
Switching value
|
input
|
2 or 4 dry contact inputs
|
||||
|
output
|
Output mode: 2 or 4-way relay normally open contact output
|
||||||
|
contact rating:AC 250V/3A、DC 30V/3A
|
|||||||
|
Analog output |
Output mode: 1 or 2-way output, (the function of transformation output shall be specified by the user)
|
||||||
|
Load capacity:≤500Ω
|
|||||||
|
temperature coefficient:
-20~55℃ 300ppm/℃ -40~-20℃ 600ppm/℃
|
|||||||
|
measurement accuracy
|
Current / voltage: class 0.2/0.5, frequency 0.01Hz
Power, active energy: 0.5, reactive energy: 1 |
||||||
|
Power Supply
|
AC85~265V or DC100~350V;power waste≤10VA
|
||||||
|
Safety |
routine |
Power frequency withstand voltage: power supply / / switching value output / / current input / / voltage input and transmission // communication / / pulse output//Ac2kv 1min between switching value inputs;
Ac2kv 1min between power supply, switching value output, current input and voltage input; ac1kv 1min between transformation,communication, pulse output and switching value input; Insulation resistance: input and output end to shell > 100m Ω |
||||
|
Special industry
|
Power frequency withstand voltage: power supply / / switching value output / / current input / / voltage input and transmission // communication / / pulse output//AC 4KV 1min between switching value inputs;
AC 4KV 1min between power supply, switch output, current input and voltage input; Ac2kv 1min between transmission, communication, pulse output and switching value input; Insulation resistance: input and output end to shell > 100m Ω |
|||||
|
Environmental Science |
routine
|
Operating temperature: – 10 ℃ ~ + 55 ℃; storage temperature:
– 20 ℃ ~ + 70 ℃ Relative humidity ~ 95 no condensation; altitude: ≤ 2500m |
||||
|
Special industry
|
Operating temperature: – 40 ℃ ~ + 55 ℃; storage temperature:
– 50 ℃ ~ + 70 ℃ Relative humidity: 5% ~ 95%, no condensation; altitude: ≤ 5000m |
|||||
|
Altitude
|
Not more than 2000 meters
|
|
ambient temperature
|
The temperature is not higher than + 65 ℃ and not lower than – 25 ℃.
|
|
relative humidity
|
The air humidity shall not exceed 90% at 20 ℃, and higher relative humidity is allowed at lower temperature.
|
|
atmospheric pressure
|
79.5Kpa ~ 106KPa
|
|
environment condition
|
The surrounding medium shall be free of explosion hazard, corrosive gas, conductive dust, rain and snow erosion, and the
installation site shall not be subject to severe vibration. |
|
Control output
|
3 way
|
|
Appearance and installation opening size (unit: mm)
|
||||||||||||||
|
Model
|
Face frame size(mm)
|
Shell size(mm)
|
Shell opening size(mm)
|
|||||||||||
|
W1 wide
|
H1 high
|
W2
|
H2
|
D thick
|
W3
|
H3
|
||||||||
|
FRDM80
|
84
|
84
|
75
|
75
|
95
|
76
|
76
|
|||||||
|
FRDM96
|
96
|
96
|
89
|
89
|
96
|
91
|
91
|
|||||||
|
FRDM120
|
120
|
120
|
110
|
110
|
82
|
111
|